d
|
|
Power and Distribution Switchboards |
![]() |
|
|
|
|
![]() Service entrance equipment with provisions for metering current transformers. |
Park standard construction utilizes
|
STANDARD ENCLOSURE DIMENSIONS | |||
| Amp Rating | W | D | H |
| 400-1000 | 34" | 24" | 90" |
| 1200-2OOO | 34" | 24" | 90" |
| 2500 | 42" | 24" | 90" |
| 3000-4000 | 44" | 30" | 90" |
| 5000-6000 | 54" | 36" | 90" |
BRANCH SWITCHES |
|||||||||||||||||||||||||||||||||||||||||||||||||||||
|
| ||||||||||||||||||||||||||||||||||||||||||||||||||||
| Ampere Rating | Connectors Suitable for Cu or Al |
| 200 | 1-#6 AWG-3OOMCM |
| 400 | 1-#3/0-500 MCM or 2-#3/0 AWG-250 MCM |
| 600 | 2-#3/0-500 MCM |
| 800 | 3-#3/0-500 MCM |
| 1200 | 4-#3/0-500 MCM |
| Ampere Rating | Connectors Suitable for Cu or Al |
| 200 | 1--#6 AWG-300 MCM |
| 400 | 1--#3/0 AWG-500 MCM or 2--#3/0 AWG-250 MCM |
| 600 | 2--#3/0-500 MCM |
| Switch Ampere Rating |
Wire & Cable Range |
| 30 | 1--#14-4 AWG (Cu or Al) |
| 60 | 1--#14-4 AWG (Cu or Al) |
| 100 | 1--#10--#1/0 AWG (Cu or Al) |
| 200 | 1--#6 AWG-350 MCM (Cu or Al) |
| 400 | 2--4/0 AWG-500 MCM (Cu or Al) |
| 600 | 2--4/0 AWG-500 MCM (Cu or Al) |
| Amperage | Main Lugs | Main Switch |
| 200 | 65 | 52.5 |
| 400 | 62.5 | 42.5 |
| 600 | 60 | 37.5 |
| 800 | 57.5 | 30 |
| 1200 | 57.5 | 30 |
| 2000 | 50 | 30 |
| 2500 | 47.5 | 30 |
|
PARK DETROIT
PARK ELECTRIC PARK FABRICATING POWER DISTRIBUTION SYSTEMS |
19197 Sherwood Avenue
Detroit, Michigan 48234 313/366-2200 Fax: 313/366-1540 Email: parkdet@ix.netcom.com |