d
PARK
ELECTRIC parknav.gif

Power and Distribution Switchboards
 
lightning2.gif

  • 250 Volts AC or DC
  • 600 Volts AC
  • 6000 Amp maximum switch
  • UL short circuit rating:
    200 kA IR maximum
Meets 1987 NEC wire bending requirement, section 373-6.
Switchboards Listed by Underwriter's Laboratories, Inc., under File #32546. Meet Federal Specification W-P-llSb dated June 8, 1984, for Type 11, Class 1.
Service 250 Volts DC, 600 Volts AC maxi- mum. I phase, 2 wire; 1 Phase, 3 Wire; 3 Phase, 3 Wire; or 3 Phase, 4 Wire.
Standard Enclosure Width is 34 inches. 30-inch wide enclosures are available upon request when branch Vacu-break [trademard goes here] switches are 200A maximum.
Standard Panel is without door. Doors are available upon request.
Motor Starters Available in switchboards.
Branch Switches Horsepower-rated fusible switch units.

Service entrance equipment with provisions for metering current transformers.

Park standard construction utilizes

  • Silver plated copper bus 650C rise
  • Heavy steel enclosures
  • Bolted electrical connections
  • Tamperproof enclosure with hinged door over current transformer compartment with latch for utility company sealing.
  • Standard with hot metering; cold metering available upon request.
  • Top & bottom feed available, bus head service available for top feed.
  • Potential transformer provisions furnished when required.
  • Manufactured to meet electric utility specifications.

PARK will make switchboards to meet your requirements

OPTIONS


APPLICATION DATA

STANDARD ENCLOSURE DIMENSIONS

Amp Rating W D H
400-1000 34" 24" 90"
1200-2OOO 34" 24" 90"
2500 42" 24" 90"
3000-4000 44" 30" 90"
5000-6000 54" 36" 90"

BRANCH SWITCHES

Ratings
Amperes
Mounting
Height
Inches
250V
Twin Units
NEC
Fuse Clips
30-30 5
30-60 5
60-60 5
60-100 7 1/2
100-100 7 1/2
250V
Single Units
NEC
Fuse Clips
200 10
400 15
600 15
600V
Twin Units
NEC
Fuse Clips
30-30 7 1/2
30-60 7 1/2
60-60 7 1/2
60-100 7 1/2
100-100 7 1/2
Ratings
Amperes
Mounting
Height
Inches
600V
Single Units
NEC
Fuse Clips
100 7 1/2
200 10
400 15
600 15
600V
Single Units
Class L
Fuse Clips
800 35
1200 35

MAIN LUG PANELS

Ampere Rating Connectors
Suitable for Cu or Al
200 1-#6 AWG-3OOMCM
400 1-#3/0-500 MCM or
2-#3/0 AWG-250 MCM
600 2-#3/0-500 MCM
800 3-#3/0-500 MCM
1200 4-#3/0-500 MCM

MAIN SWITCH PANELS

Ampere Rating Connectors
Suitable for Cu or Al
200 1--#6 AWG-300 MCM
400 1--#3/0 AWG-500 MCM or
2--#3/0 AWG-250 MCM
600 2--#3/0-500 MCM

BRANCH SWITCH CONNECTORS

Switch
Ampere Rating
Wire & Cable Range
30 1--#14-4 AWG (Cu or Al)
60 1--#14-4 AWG (Cu or Al)
100 1--#10--#1/0 AWG (Cu or Al)
200 1--#6 AWG-350 MCM (Cu or Al)
400 2--4/0 AWG-500 MCM (Cu or Al)
600 2--4/0 AWG-500 MCM (Cu or Al)

ENCLOSURE CIRCUIT SPACE DATA

Amperage Main Lugs Main Switch
200 65 52.5
400 62.5 42.5
600 60 37.5
800 57.5 30
1200 57.5 30
2000 50 30
2500 47.5 30
Home | 600V Power Gear | Switchboards | 15 kV LI Gear | Busway


park4.gif PARK DETROIT
PARK ELECTRIC
PARK FABRICATING
POWER DISTRIBUTION SYSTEMS
19197 Sherwood Avenue
Detroit, Michigan 48234
313/366-2200
Fax: 313/366-1540
Email: parkdet@ix.netcom.com

Send Us Email

Comments to jnr at Insight Web Designs